麦科信

Rogowski AC Current Probe Rogowski AC Current Probe

Bandwidth: 2Hz–10MHz
Minimum Coil Cross-section (diameter): 8mm
Typical Accuracy: 2%
Peak Current: 12000Apk
Interface: BNC

  • Overview

  • Document

  • Download

  • Features

  • Specifications

  • Documents

productdetail

The Micsig RCP series Rogowski current probe measures AC currents up to 12000 Apk, offers a maximum bandwidth of 30MHz. With nearly zero insertion impedance, the probes minimize interference to the circuit under test. The coils exhibit high voltage resistance (up to 10 kVpk) and support customization of coil cross-sectional diameter, perimeter, and lead length to accommodate complex application scenarios.



It features a standard BNC interface for use with any oscilloscope. Its compact, flexible design easily solves the hard-to-reach part issue, and the coil diameter supports customization to meet more test requirements.

Measure the Id current of MOSFET

Measure the Id current of MOSFET


The RCP has excellent high-frequency measurement capabilities, easily handles high-speed signals and rapidly changing current waveforms, helping to observe high-frequency harmonic components when measuring the Id current of MOSFETs.

(Signal measured with the RCP600XS-80)

BNC interface

BNC interface


Standard BNC interface to use on any oscilloscope.

Applications

Applications


● Measuring current in motor drives and in particular power quality measurements in VSD, UPS or SMPS circuits
● Double-pulse testing to measure the pin currents of MOSFET and IGBT chips made of materials such as SiC and GaN
● Measurement of load current and high-order harmonic current in power electronics
● Measuring high frequency sinusoidal, pulsed or transient currents
● Measuring AC currents in 3-phase supply system
● Measuring the power consumption in semiconductors
● Measurement of 50/60Hz power frequency current
● Power converter development and diagnostics

Model

RCP-L Series

Coil Cross-Section Diameter

8.0 mm

Rogowski Coil Circumference

RCP***L-700: 700 mm

Accuracy (Typical)

2%

Power Supply

DC 12 V

Cable Length

1.5 m (from integrator to Rogowski coil), customizable

Output Impedance

1 MΩ

Interface

Standard BNC, compatible with all oscilloscope brands


RCP-L Series

Peak Current

Bandwidth

Output Sensitivity

Peak di/dt

Peak Coil Isolation Voltage

RCP600L-700

600Apk

8Hz-10MHz

10mV/A (100X)

70kA/μs

10kVpk (Rogowski coil only)

RCP1200L-700

1200Apk

6Hz-10MHz

5mV/A (200X)

70kA/μs

RCP3000L-700

3000Apk

4Hz-10MHz

2mV/A (500X)

70kA/μs

RCP6000L-700

6000Apk

3Hz-10MHz

1mV/A (1000X)

70kA/μs

RCP12000L-700

12000Apk

2Hz-10MHz

0.5mV/A (2000X)

70kA/μs


User Manual - RogowskiAC Current Probe RCPSeries

User Manual - RogowskiAC Current Probe RCPSeries

File size: 1.16 MB

Update time: 2026-08-04

Brochure - Rogowski AC Current Probe RCP Series

Brochure - Rogowski AC Current Probe RCP Series

File size: 1.22 MB

Update time: 2026-08-04

license